Control panels for command or protection of one or plus pumps or motors

Informazioni

Control panels for command or protection of one or plus pumps or motors

Control panels for command or protection of one or plus pumps or motors

Control panels for command or protection of one or plus pumps or motors There are no products in this category.

Subcategories

  • SMART EVO 1

    Technical features

    • Single phase power supply 100-240Vac ±10% 50/60Hz (SMART EVO Mono);
    • Three phase power supply 100-240Vac ±10% 50/60Hz (SMART EVO -Tri);
    • Three phase power supply 310-450Vac ±10% 50/60Hz (SMART EVO -Tri);
    • G/P1 and G/P2 normally open inputs for start-up command;
    • 3 inputs for single-pole level sensors (COM-MIN-MAX);
    • T1 and T2 inputs for motor clicson;
    • Normally open input for alarm activation;
    • AUTOMATIC-0-MANUAL buttons (spring return);
    • DIP-SWITCH selectors for:
      • level alarm enable from sensors,
      • thermal cut-out activation delay 5/10 seconds,
      • alarm output settings,
      • alarm reset enable from motor clicson,
      • Filling/Emptying mode,
      • start/stop float enable,
      • enable of delay on board activation on power mains return,
      • motor switching module enable (on SMART EVO 2);
    • Green led: power ON  / failure or incorrect phase sequence;
    • Green leds: automatic mode enabled;
    • Green led: motor active;
    • Red led: level alarm from sensors or GA input;
    • Red leds: motor overload alarm/minimum current alarm;
    • Red leds: motor clicson activation alarm;
    • Electronic control of maximum current due to overload, with assisted calibration;
    • Electronic control of minimum current due to dry run, with assisted calibration;
    • Automatic reset due to minimum current alarm;
    • Protections of auxiliary circuits and motor with fuses;
    • Cumulative alarm output with voltage-free contacts (COM-NO-NC resistive load - 5A / 250V);
    • Cumulative alarm output, live (12Vcc / 100mA);
    • Door lock general disconnect switch;
    • Provision for start-up capacitors, single phase version (not included);
    • Box in ABS, IP55;
    • Ambient temperature: -5/+40 °C;
    • Relative humidity 50% at 40 °C (condensate free).

  • Accessori SMART 2
  • SMART EVO 2

    Technical features

    • Single phase power supply 100-240Vac ±10% 50/60Hz (SMART EVO Mono);
    • Three phase power supply 100-240Vac ±10% 50/60Hz (SMART EVO -Tri);
    • Three phase power supply 310-450Vac ±10% 50/60Hz (SMART EVO -Tri);
    • G/P1 and G/P2 normally open inputs for start-up command;
    • 3 inputs for single-pole level sensors (COM-MIN-MAX);
    • T1 and T2 inputs for motor clicson;
    • Normally open input for alarm activation;
    • AUTOMATIC-0-MANUAL buttons (spring return);
    • DIP-SWITCH selectors for:
      • level alarm enable from sensors,
      • thermal cut-out activation delay 5/10 seconds,
      • alarm output settings,
      • alarm reset enable from motor clicson,
      • Filling/Emptying mode,
      • start/stop float enable,
      • enable of delay on board activation on power mains return,
      • motor switching module enable (on SMART EVO 2);
    • Green led: power ON  / failure or incorrect phase sequence;
    • Green leds: automatic mode enabled;
    • Green led: motor active;
    • Red led: level alarm from sensors or GA input;
    • Red leds: motor overload alarm/minimum current alarm;
    • Red leds: motor clicson activation alarm;
    • Electronic control of maximum current due to overload, with assisted calibration;
    • Electronic control of minimum current due to dry run, with assisted calibration;
    • Automatic reset due to minimum current alarm;
    • Protections of auxiliary circuits and motor with fuses;
    • Cumulative alarm output with voltage-free contacts (COM-NO-NC resistive load - 5A / 250V);
    • Cumulative alarm output, live (12Vcc / 100mA);
    • Door lock general disconnect switch;
    • Provision for start-up capacitors, single phase version (not included);
    • Box in ABS, IP55;
    • Ambient temperature: -5/+40 °C;
    • Relative humidity 50% at 40 °C (condensate free).

  • DRYTEK
    • Power supply 1~50/60 Hz 230V ±10% (DRYTEK-Mono);

    • Power supply 3~50/60 Hz 400V ±10% (DRYTEK-Tri);

    • Normally open contact for start;

    • Additional normally open contact for enabling of start;

    • Pushbuttons for selecting operation and set up;

    • Green led indicating motor running;

    • Displaying of: volt, ampere, motor COS Ø and alarms;

    • Motor’s control on 2 phases;

    • Protection from:

      - Motor overcurrent (adjustable) - Phase failure/loss
      - Min/max voltage
      - Min/max current

    • Adjustable COS Ø for dry running protection;

    • Auto-restore from protection with 4 independently settable times from

      0÷250 minutes;

    • Auxiliaries and motor protection fuses;

    • Main switch interlocking door;

    • Running capacitor can be added (optional);

    • Enclosure in ABS, IP55;

    • Ambient temperature: -5/+40 °C;

    • Relative humidity 50% at 40 °C (not condensed). 

  • Accessori DRYTEK
  • DIRECTO 1
    • Power supply 1~50/60 Hz 230V ±10% (DIRECTO1-Mono);

    • Power supply 3~50/60 Hz 400V ±10% (DIRECTO1-Tri);

    • Auxiliaries contacts and circuits in low voltage;

    • Normally open contact for start;

    • Normally open contact for minimum level/pressure contact;

    • Selector for Auto-O -Manual (stable) operation;

    • Blue led indicating mains supply;

    • Green led indicating motor running;

    • Red led indicating motor overload;

    • Line contactor in AC3;

    • Overload thermal relay internally restorable;

    • Auxiliaries and motor protection fuses;

    • Main switch interlocking door;

    • Enclosure in ABS up to 15 HP, steel enclosure from 20 to 50 HP, IP55;

    • Ambient temperature: -5/+40 °C;

    • Relative humidity 50% at 40 °C (not condensed). 